Parameter reference
8.6 Setup (2.)
HydroRanger 200 HMI
Operating Instructions, 06/2018, A5E36281317-AC
237
The factory setting is for optimum visibility at room temperature and in average lighting
conditions. Extremes of temperature will lessen the contrast. Adjust the value to improve
visibility in different temperatures and lighting conditions.
8.6.12.3
Level selector (2.12.3.)
Sets the Level Point index for all parameters applicable to this sub-menu.
8.6.12.4
Decimal position (2.12.4.)
Defines the maximum number of decimal places used on the LCD.
Index
Level
Options
No digits
1 digit
*2 digits
3 digits
Alters
Flowrate decimal (2.13.4.6.) (Page 245)
Altered by
Maximum volume (2.7.3.) (Page 188)
Related
Reading (3.2.8.2.) (Page 256)
In RUN mode, the decimal position adjusts to prevent the number of digits from exceeding
the display capabilities. To keep the decimal place from shifting, reduce the number of
decimal places to that shown at 100%.
Example:
If 100% is 15 m, use two decimal places for sample readings of
15.00
or
12.15
.