Communications
C.8 Communications installation
HydroRanger 200 HMI
324 Operating Instructions, 06/2018, A5E36281317-AC
C.8
Communications installation
C.8.1
Wiring guidelines
The RJ-11 cable maximum length is 3 meters.
RS-485 maximum length is 1 200 meters (4 000 feet).
Use 24 AWG (minimum).
Use good quality communication grade (shielded twisted pairs) cable that is
recommended for RS-485 for port 2 (Belden 9842).
Run the communication cable separately from power and control cables (do not tie wrap
your RS-232 or RS-485 cable to the power cable or have them in the same conduit).
Use shielded cable and connect to ground at one end only.
Follow proper grounding guidelines for all devices on the bus.
Note
Improper wiring and incorrect choice of cables are two of the most common causes of
communication problems.
Ports 1 and 2
Port
Wall mount
1 RS-232 port (RJ-11 modular telephone jack) is generally used with a laptop computer or mo-
dem.
2
Connections for the RS-485 port are on the terminal block.
Ports 1 and 2: RS-232 RJ-11 jack and RS-485 locations
The RJ-11 jack and the RS-485 port are inside the enclosure of the unit.