Parameter reference
8.6 Setup (2.)
HydroRanger 200 HMI
Operating Instructions, 06/2018, A5E36281317-AC
185
Shows the time constant used in the mA input filter to dampen signal fluctuations.
Range: 0 ... 9999 seconds
Preset: 1 second
This number is used in the damping calculations. Larger values damp more than smaller
values and 0 disables the signal filter.
Scaled mA input value (2.6.5.)
Shows the resulting level value after scaling.
Global
Range: -999 ... 9999% (read only)
Preset: calculated from the input mA signal
Raw mA input value (2.6.6.)
Shows the raw mA input supplied by an external device.
Range: 0.000 ... 20.00 (Read only)
Carries out a volume conversion from a Level measurement.
Sets the Level Point index for all parameters applicable to this sub-menu.