Parameter reference
8.6 Setup (2.)
HydroRanger 200 HMI
Operating Instructions, 06/2018, A5E36281317-AC
185
8.6.6.4
mA Damp Filter (2.6.4.)
Shows the time constant used in the mA input filter to dampen signal fluctuations.
Index
Global
Values
Range: 0 ... 9999 seconds
Preset: 1 second
This number is used in the damping calculations. Larger values damp more than smaller
values and 0 disables the signal filter.
8.6.6.5
Scaled mA input value (2.6.5.)
Shows the resulting level value after scaling.
Index
Global
Values
Range: -999 ... 9999% (read only)
Preset: calculated from the input mA signal
8.6.6.6
Raw mA input value (2.6.6.)
Shows the raw mA input supplied by an external device.
Index
mA Input
Values
Range: 0.000 ... 20.00 (Read only)
8.6.7
Volume (2.7.)
Carries out a volume conversion from a Level measurement.
8.6.7.1
Level selector (2.7.1.)
Sets the Level Point index for all parameters applicable to this sub-menu.