5.5 Transducers
HydroRanger 200 HMI
42 Operating Instructions, 06/2018, A5E36281317-AC
5.5
Transducers
WARNING
Hazardous voltage on transducer terminals during operation
Using a co-axial transducer cable extension with the device is NOT recommended
1)
Do not connect the shield and white transducer wires together; wire to separate
terminals.
Disregard older transducer manuals that recommend practices different from those
listed above
1)
If it is really necessary to use such cable, see Co-axial transducer extension (Page 354) for
instructions.
A 0.1 μF (100 V or greater) capacitor is included with the device for retrofitting older
installations. For instruction on how to use a co-axial cable, see Co-axial transducer
extension (Page 354)