Operating
7.3 Relays
HydroRanger 200 HMI
100 Operating Instructions, 06/2018, A5E36281317-AC
7.3.9
Preset applications
Preset applications set up the relay parameters to predetermined values shown below:
OFF:
all relays set to OFF
Wet Well 1
Pump down with the following settings:
Parameter
Relay #
1
2
3
4
5
6
Relay Function
(2.8.1.4.)
(Page 195)
Alternate Duty
Assist
Alternate Duty
Assist
Level (H) Level (L) OFF OFF
ON Setpoint
(2.8.1.5.)
(Page 197)
70% 80% 90% 10% -- --
OFF Setpoint
(2.8.1.6.)
(Page 197)
20% 20% 85% 15% -- --