Discrete input 2 scaled state (3.3.1.4.)
Shows the current value of the discrete input after any scaling is applied. Read only.
Discrete Input
Inactive
Readings are updated continuously even in PROGRAM mode. The value signals a level
override event.
The device communications ports are configured by a series of parameters that are indexed
by port. See Communications (Page 321) for a complete description of the communications
set-up.
Unless otherwise noted, communication parameters are indexed to the following
communications ports:
RS-232 port (RJ-11 modular telephone)
RS 485 port on terminal block
Communications port selector (4.1.)
Sets the communications port index for all parameters applicable to this sub-menu.
Sets the unique identifier of the device on the network.
For devices connected with the Siemens protocol, this parameter is ignored. For devices
connected with a serial Modbus slave protocol, this parameter is a number from 1-247. The
network administrator must ensure that all devices on the network have unique addresses.
Do not use the value 0 for Modbus communications as this is the broadcast address and is
inappropriate for a slave device.