Operating
7.8 Alarms
HydroRanger 200 HMI
116 Operating Instructions, 06/2018, A5E36281317-AC
Use the temperature alarm to activate an alarm when the temperature reaches the ON
setpoint (2.8.1.5.) (Page 197). This alarm uses the same setpoint parameters as the level
alarms [ON Setpoint (2.8.1.5.) (Page 197) and OFF Setpoint (2.8.1.6.) (Page 197) ]
You can set a high alarm (ON Setpoint > OFF Setpoint) or a low alarm (ON Setpoint < OFF
Setpoint).
Relay Function (2.8.1.4.)
5 Temperature Alarm on temperature
ON Setpoint (2.8.1.5.)
(Page 197)
5 45 ON setpoint at 45 °C
OFF Setpoint (2.8.1.6.)
5 43 OFF setpoint at 43 °C
Level Source (2.8.1.2.)
5 Transducer 1 Take the temperature reading from Trans-
The temperature source can be the temperature sensor built into the transducer or an
external TS-3, as set by Temperature Source (2.11.1.4.). (Page 219)
Activates an alarm when the device loss of echo timer passes without detecting a valid echo.
Level Source (2.8.1.2.)
5 Transducer 1 Alarm on LOE for Transducer 1
Relay Function (2.8.1.4.)
5 LOE Alarm on LOE
LOE Timer (2.4.2.)
Global 0.5 Trip alarm when 0.5 minutes (30 seconds)
pass without detecting a valid echo.