Commissioning
6.7 Application examples
HydroRanger 200 HMI
88 Operating Instructions, 06/2018, A5E36281317-AC
6.7.1
Level application
Space 7.5 m
15.0 m
1.0 m
Empty
Span
Range extension
Distance 8.5 m
Level 6.5 m
Sensor reference point
Quick Start parameter
Setting
Description
Transducer
XPS-15
Transducer to be used with the device
Operation
Level
Material level referenced from Low Cal. Point
Temperature Source
TS-3
Temperature source
Units
m
Sensor measurement units
Empty
15.0
Process empty level
Span
1.0
Process full level
Response Rate
Slow
Sets Fill Rate
1
/ Empty Rate to 0.1 m/minute
1
See Fill rate/minute (2.3.2.) (Page 173)
The application is a vessel that takes an average 3 hours (180 minutes) to fill and 3 weeks to
empty.
Fill rate = (Empty Span) / fastest of fill or empty time
= (15.5 m 1 m) / 180 min.
= 14.5 m /180 min. = 0.08 m/min.