Parameter reference
8.6 Setup (2.)
HydroRanger 200 HMI
182 Operating Instructions, 06/2018, A5E36281317-AC
8.6.5.5
4 mA setpoint (2.5.5.)
Sets the process level corresponding to the
0 or 4 mA
value.
Index
mA Output
Values
Range: -999 ... 9999
Related
20 mA setpoint (2.5.6.) (Page 182)
Enter the value [in applicable Units (2.1.1.) (Page 162)] to correspond to
0 or 4 mA
.
8.6.5.6
20 mA setpoint (2.5.6.)
Sets the process level that corresponds to the
20 mA
value.
Index
mA Output
Values
Range: -999 ... 9999
Related
4 mA setpoint (2.5.5.) (Page 182)
Enter the value [in applicable Units (2.1.1.) (Page 162)] to correspond to
20 mA
.
8.6.5.7
Minimum mA limit (2.5.7.)
Sets the minimum mA output value to be produced.
Index
mA Output
Values
Range: 0.000 .. 22.000 mA
Preset: 3.800 mA
Related
mA output range (2.5.2.) (Page 180)
Maximum mA limit (2.5.8.) (Page 182)
8.6.5.8
Maximum mA limit (2.5.8.)
Sets the maximum mA output value to be produced.
Index
mA Output
Values
Range: 0.000 ... 22.000 mA
Preset: 20.200 mA
Related
mA output range (2.5.2.) (Page 180)
Minimum mA limit (2.5.7.) (Page 182)
8.6.5.9
Milliamp output (2.5.9.)
Displays the current mA output value.
Range: 3.500 ... 22.2 mA