EasyManua.ls Logo

Siemens HydroRanger 200 HMI - Sensor Mode (2.1.3.)

Siemens HydroRanger 200 HMI
404 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameter reference
8.6 Setup (2.)
HydroRanger 200 HMI
Operating Instructions, 06/2018, A5E36281317-AC
163
8.6.1.3
Sensor mode (2.1.3.)
Sets the type of measurement required for the application.
Index
Single-point model
Dual-point model
Global
Transducer
Options (mode)
Out of service
*Level how full the vessel is; default for dual-
point model
Space
how empty the vessel is
*Distance distance from transducer to material;
default for single-point model
Dual-point difference
DPD
Dual-point average
DPA
Flow rate in open channel
OCM
Pump totalizer
total pumped volume
Alters
Primary measuring device (2.13.2.) (Page 240)
Dual-Point Difference (DPD) and Dual-Point Average (DPA)
Single-point model use
For DPD or DPA, the unit requires either two transducers of the same type, or one
transducer and one mA input. If two transducers are used, all transducer parameters
become indexed, and a third level point is calculated.
DPD (difference) = Point 1 - Point 2
DPA (average) = (Point 1 + Point 2)/2. The calculated DPD or DPA is always based on
level measurements of Points 1 and 2.
For these operations any of three level points (Transducer 1, Transducer 2, or the calculated
point) can be used to trigger relays [Level source (2.8.1.2.) (Page 194)].
The points must be globally set to either Dual-Point Difference or Dual-Point Average, as
required. Point 3 becomes the calculated value as shown above. See Setting a rake control
(Page 132).
Dual-point model use
To set a dual-point device for DPD or DPA functions, Point 3 must be set to either Dual-Point
Difference or Dual-Point Average, as required. Points 1 and 2 cannot be set do Dual-Point
Difference or Dual-Point Average, but these points are used to calculate the value in Point 3.
The calculated DPA is always based on level measurements of Points 1 and 2.
This table shows the available functions:
Operation
Index
Available options
Sensor Mode (2.1.3.)
1 *Level, Space, *Distance, Flow rate in open channel, Pump
Totalizer
2 *Level, Space, *Distance, Flow rate in open channel, Pump
Totalizer
3
Dual-Point Difference, Dual-Point Average

Table of Contents

Related product manuals