Communications
C.11 Word order (R40,062)
HydroRanger 200 HMI
Operating Instructions, 06/2018, A5E36281317-AC
329
Type
Description
Start
#R
1
Data type
Read/write
Point data
Temperature (2)
41,030
2
50 ... 150
R
Totalizer for Points
1 and 2
41,040 4 UINT32 R/W
I/O
Discrete Inputs (2)
41,070
1
Bit Mapped
R
Relay Outputs (3 or
6)
41,080 1 Bit Mapped R/W
mA Input (1)
41,090
1
0000 ... 20,000
R
mA Output (2)
41,110
2
0000 ... 20,000
R/W
Pump control
Pump ON Setpoint
(3 or 6)
41,420 6 0000 ... 10,000 R/W
Pump OFF Setpoint
(3 or 6)
41,430 6 0000 ... 10,000 R/W
Pumped Volume (2)
41,440
4
UINT32
R
Pump Hours (3 or 6)
41,450
12
UINT32
R
Pump Starts (3 or 6)
41,470
6
0000 ... 10,000
R
Parameter access
43,998 ... 46,999
R/W
1
Maximum registers shown; fewer may be used depending on options installed.
The device was designed to make it easy for master devices to get useful information via
Modbus. This chart gives an overview of the different sections. A more detailed explanation
of each section follows below.
C.11
Word order (R40,062)
This determines the format of unsigned, double-register integers (UINT32).
0
indicates that the most significant word (MSW) is given first
1
indicates that the least significant word (LSW) is given first
See Unsigned double precision integer (UINT32) (Page 340) for more information.
C.12
Map ID (R40,063)
This value identifies the register map used by the device. See Parameter Index Location
(4.11.) (Page 270) and Parameter access (R43,998-R46,999) (Page 333) for details.