7.9 Pump control
HydroRanger 200 HMI
Operating Instructions, 06/2018, A5E36281317-AC
119
7.9.2
Setting a pump up (reservoir) group
Set a group of three pumps to pump up a reservoir.
Inflow
Transducer
Span (2.2.2.) (Page 169)
Outflow
Empty (2.2.4.) (Page 170)
Set the common parameters
Prerequisite:
Substitute the details of your application in place of the sample values
provided. If you are bench testing the unit, set your test values to be the same as the sample
values.
Parameter
Index
1
Value/Mode
Description
Sensor Mode (2.1.3.)
(Page 163)
Global *Level (Page 163) Operation=*Level (Page 163)
Material (2.1.6.)
(Page 165)
Global Liquid Material = *Liquid
Response Rate (2.3.4.)
(Page 174)
Global Medium Maximum Process Speed = *Medium
(1.0 m/min) (Page 174)
Transducer (2.1.5.)
(Page 164)
Global XPS-10 Transducer = XPS-10 (single-point
preset)
Units (2.1.1) (Page 162)
Global
-
Units = Meters
Empty (2.2.4.)
(Page 170)
Global 1.8 Empty = 1.8 m
Span (2.2.2.) (Page 169)
Global
1.4
Span = 1.4 m
1
Example assumes a single measurement unit. If your device has dual-point software
installed, then some parameters are indexed by two level points.