Parameter reference
8.7 Maintenance and Diagnostics (3.)
HydroRanger 200 HMI
256 Operating Instructions, 06/2018, A5E36281317-AC
Corresponds to the final reading after all programming is applied.
Level
In general, this means that: Reading (3.2.8.2.) = [Reading x Convert Reading (2.12.5.)
(Page 238)] + Offset Reading (2.12.6.) (Page 238).
Reading measurements by operation:
OFF ---- ----
Level (3.2.8.3.) (Page 256)
Head (3.2.8.13.) (Page 258)
Space Space (3.2.8.11.) (Page 258) 100% minus Head (3.2.8.13.)
Distance Distance (%) (3.2.8.4.)
Distance (%) (3.2.8.4.)
Level (3.2.8.3.) (Page 256)
Level (3.2.8.3.) (Page 256)
Level (3.2.8.3.) (Page 256)
Level (3.2.8.3.) (Page 256)
Flow (3.2.8.14.) (Page 259)
Flow (3.2.8.14.) (Page 259)
Head (3.2.8.13.) (Page 258)
Head (3.2.8.13.) (Page 258)
Shows the distance in Units (2.1.1.) (Page 162) between Empty (2.2.4.) (Page 170) and the
monitored surface.
• Units (2.1.1.) (Page 162)
• Empty (2.2.4.) (Page 170)
• Span (2.2.2.) (Page 169)
Shows the distance between the surface and the transducer face (displays only as % of
Empty).
Range: 0.000 ... 9999% (Displays as % of Empty; Read only)
• Units (2.1.1.) (Page 162)
• Empty (2.2.4.) (Page 170)
Use Distance (3.2.8.12.) (Page 258) unless the distance information is required in percent.