Parameter reference
8.6 Setup (2.)
HydroRanger 200 HMI
234 Operating Instructions, 06/2018, A5E36281317-AC
Down sampling (2.11.5.3.)
Sets the number of consecutive echoes that must occur below the echo currently locked
onto before the measurements are validated as the new reading [for Echo Lock (2.11.5.4.)
(Page 235) = Maximum verification or Material agitator]
Range: 1 ... 50
• Echo lock (2.11.5.4.) (Page 235)
• Up sampling (2.11.5.2.) (Page 233)
Echo Lock (2.11.5.4.) (Page 235)
● Echo Lock (2.11.5.4.) (Page 235) = Material agitator
● Up Sampling (2.11.5.2.) (Page 233) = 5
● Down sampling (2.11.5.3.) = 2
Result:
● Five consecutive measurements higher than the current reading will validate a new
reading.
OR
● Two consecutive measurements lower than the current reading will validate a new
reading.
Resetting Echo Lock (2.11.5.4.) (Page 235) returns Up Sampling (2.11.5.2) (Page 233) and
Down Sampling ( 2.11.5.3.) to their respective preset values.