Drive functions
7.3 Function modules
Function Manual
216 Function Manual, 01/2011, 6SL3097-4AB10-0BP3
> @
> @
[ ]
1
r1229.10
p1279[0]
p127 9[1 ]
r122 9.3
<1>
p1275.02 (1)
1
0
1
p122 4[0 ]
<1>
r0898.6
&
p1142[C]
(r0899.15)
p1152
<1>
[2501 ]
p0856
3XOVHHQDEOH
H[WEUDNHFRQWURO
25ORJLFRSHUDWLRQ
%UDNH
25ORJLFRSHUDWLRQ
UHVXOW
(QDEOHVSHHGFRQWUROOHU
(QDEOHQBVHW
6HWSRLQWHQDEOH
(QDEOHVSHHGVHWSRLQW
%UDNHWRVWDQGVW
!6HWSRLQWHQDEOHIURPKLJKHUOHYHO
FRQWUROOHUHJ6
 (QDEOHVHWSRLQW
0DVWHUVZLWFKPRYHG
>[[[[@)XQFWLRQGLDJUDPQXPEHU
Figure 7-38 Example, operating brake for a crane drive
7.3.4.5 Commissioning
The extended brake control function can be activated while the commissioning Wizard is
running. Parameter r0108.14 indicates whether the function module has been activated.
Unless you change the default settings, the extended brake control function behaves in
exactly the same way as the simple brake control function.
Brake control can be activated via a parameter (p1215 = 3).
When braking with a feedback signal (p1222), the inverted signal must be connected to the
BICO input for the second (p1223) feedback signal. The response times of the brakes can
be set in p1216 and p1217.
Note
If p1215 = 0 (no brake available) is set when a brake is present, the drive runs with applied
brake. This can damage the brake beyond repair.
CAUTION
Brake control monitoring may only be activated for Blocksize power units with Safe Brake
Relay (p1278 = 0).