Safety Integrated Functions
8.5 Safety Integrated Extended Functions
Function Manual
Function Manual, 01/2011, 6SL3097-4AB10-0BP3
387
8.5.7.3 Safe Speed Monitor restart
Restart after pulse suppression for p9309/p9509 = 0
If the drive pulses have been suppressed using OFF1/OFF2/STO, the following steps must
be carried out for a restart:
1st scenario:
State after power-on:
SSM selected,
STO selected,
Pulse suppression active
Deselect STO.
A drive enable via a positive edge at OFF1 must occur within 5 seconds after deselection
of the STO, otherwise the drive will drop back into the STO state.
2nd scenario
Situation:
SSM selected
Motor turning
OFF1 triggered, pulses are suppressed
Select STO
Deselect STO.
STO activated internally via pulse suppression: This activation must be undone by
selection/deselection.
A drive enable via a positive edge at OFF1 must occur within 5 seconds after deselection
of the STO, otherwise the drive will drop back into the STO state.