Drive functions
7.3 Function modules
Function Manual
Function Manual, 01/2011, 6SL3097-4AB10-0BP3
307
7.3.8.14 PDE (ON delay)
Brief description
BOOL-type timer with ON delay
Mode of operation
The rising edge of a pulse at input I sets output Q to 1 after pulse delay time T.
Output Q become 0 when I is 0.
If the duration of input pulse I is less than pulse delay time T, Q remains 0.
If time T is so long that the maximum value that can be displayed internally (T/ta as 32 bit
value, where ta = sampling time) is exceeded, the maximum value is set (e.g. when ta = 1
ms, approx. 50 days).
Time flow chart
Output pulse Q as a function of pulse duration T and input pulse I.
TT
I
Q
0
1
0
1
T
Figure 7-74 PDE (ON delay): Time flow chart