Commissioning with PROFIBUS
3.3 Basic Operator Panel 20 (BOP20)
Function Manual
52 Function Manual, 01/2011, 6SL3097-4AB10-0BP3
3.3.1 Important functions via BOP20
Description
Using the BOP20, the following functions can be executed via parameters that support you
when handling projects:
Restoring the factory settings
Copy RAM to ROM
Acknowledge error
Restoring the factory settings
The factory setting of the complete device can be established in the drive object CU.
p0009 = 30
p0976 = 1
Copy RAM to ROM
You can initiate the saving of all parameters to the non-volatile memory in the drive object
CU:
Press the P key for 3 seconds,
or
p0009 = 0
p0977 = 1
NOTICE
This parameter is not accepted if an identification run (e.g. motor identification) has
been selected on a drive.
Acknowledge error
To acknowledge all the faults that have been rectified, press the Fn key.