Safety Integrated Functions
8.7 Commissioning
Function Manual
428 Function Manual, 01/2011, 6SL3097-4AB10-0BP3
8.7.2 Commissioning of Safety Integrated functions
8.7.2.1 General information
PROFIsafe commissioning with STARTER
1. The Safety Integrated Basic Functions can be commissioned using STARTER in three
ways:
STO/SS1/SBC via terminals
STO/SS1/SBC via PROFIsafe
STO/SS1/SBC via PROFIsafe and terminals simultaneously
2. The Safety Integrated Extended Functions can be commissioned using STARTER in
three ways:
Motion Monitoring via terminal
Motion monitoring via PROFIsafe
Motion monitoring via PROFIsafe and terminal simultaneously
There follows a brief overview of the STARTER functionality which enables Safety Integrated
Functions to be used by means of terminals, PROFIsafe, or a combination of the two.
Safety slot
In order to use Safety Integrated functions via PROFIBUS or PROFINET, a safety slot must
first be created using SIMATIC Manager Step 7 and HW Config. The procedure to do this
was described in the previous chapters.
Expert list
The Safety Integrated Basic Functions can be individually and manually set using the Expert
list; the settings using the STARTER screen forms, however, are more user-friendly and you
are less prone to making mistakes.