Diagnostics
5.1 Diagnostics via LEDs
Function Manual
92 Function Manual, 01/2011, 6SL3097-4AB10-0BP3
5.1.4 Meaning of LEDs on the Sensor Module Cabinet-Mounted SMC30
Table 5- 4 Meaning of LEDs on the Sensor Module Cabinet SMC30
LED Color Status Description, cause Remedy
- Off Electronics power supply is missing or outside permissible
tolerance range.
Green Continuous
light
The component is ready for operation and cyclic DRIVE-
CLiQ communication is taking place.
Orange Continuous
light
DRIVE-CLiQ communication is being established.
Red Continuous
light
At least one fault is present in this component.
Note:
The LED is activated regardless of whether the
corresponding messages have been reconfigured.
Remedy and
acknowledge fault
Green/re
d
Flashing
0.5 Hz
Firmware is being downloaded.
Green/re
d
Flashing 2
Hz
Firmware download is complete. Wait for POWER ON. Carry out a POWER
ON
RDY
READY
Green/or
ange
or
Red/oran
ge
Flashing
light
Component recognition via LED is activated (p0144).
Note:
Both options depend on the LED status when component
recognition is activated via p0144 = 1.
- Off Electronics power supply is missing or outside permissible
tolerance range.
Power supply ≤ 5 V.
OUT > 5 V
Orange Continuous
light
Electronics power supply for encoder system available.
Power supply > 5 V.
Important:
Make sure that the connected encoder can be operated
with a 24 V power supply. If an encoder that is designed
for a 5 V supply is operated with a 24 V supply, this can
destroy the encoder electronics.