EasyManua.ls Logo

Siemens SINAMICS S110 - Interface description

Siemens SINAMICS S110
714 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Commissioning with CANopen
4.2 Commissioning
Function Manual
Function Manual, 01/2011, 6SL3097-4AB10-0BP3
71
4.2.2 CANopen object directory
CANopen object directory
When the drive objects are initialized, the CANopen objects are initialized in the object
directory for the SINAMICS drive line-up (CANopen slave software).
Objects
The following SINAMICS objects are involved in communication:
1. Control Unit communication objects independent of the drive
include: Number and number of errors, communication addresses etc.
2. Drive-dependent communication objects
Up to eight PDOs for sending and eight PDOs for receiving can be parameterized for
the drive. Each PDO contains:
- Communication and
- Mapping parameters (max. 8 bytes/4 words/64 bits)
3. Manufacturer-specific objects
Objects for accessing SINAMICS parameters
Free objects for sending/receiving process data, there are freely interconnectable
objects available for each drive object (max. 16) in the object directory (see CANopen
manual for table).
The manufacturer-specific range starts in the object directory from address 2000 hex
and ends at 5FFF hex.
4. Drive objects in drive profile DSP 402
Profile velocity mode
Setpoint and actual values and comparisons

Table of Contents

Other manuals for Siemens SINAMICS S110

Related product manuals