Safety Integrated Functions
8.9 Acceptance test and acceptance report
Function Manual
Function Manual, 01/2011, 6SL3097-4AB10-0BP3
463
8.9.2.2 Content of the partial acceptance test
A) Documentation
Documentation of the machine and of safety functions
1. Extending/changing the hardware data
2. Extending/changing the software data (specify version)
3. Extending/changing the configuration diagram
4. Extending/changing the function table:
Active monitoring functions depending on the operating mode and the protective door
Other sensors with protective functions
The table is part or is the result of the configuring work
5. Extending/changing the SI functions per drive
6. Extending/changing the specifications of the safety equipment
B) Functional testing of safety functions
Detailed function test and evaluation of SI functions used. For some functions this contains
trace recordings of individual parameters. The procedure is described in detail in section
Acceptance tests.
The function test can be left out if no parameters of the individual safety functions have been
changed. In the case that only parameters of individual functions have been changed, only
these functions need to be tested anew.
1. Test of the SI function "Safe Torque Off" (STO)
Required when used in Basic and/or Extended Functions
This test is also required if you are not explicitly using STO, but just one function for
which STOP A occurs as an error response.
Alternatively, you can also carry out the quantitative test using STOP A yourself, if you
use the tables from sections Acceptance test Safe Torque Off (Bas
ic Func
tions)
(Page 475) , Acceptance test Safe Torque Off with encoder (Extended Functions)
(Page 481) or Acceptance test Safe Torque Off without encoder (E
xtended Functions)
(Page 509).
You do not n
eed to prepare trace
recording for this test.
2. Test of the SI function "Safe Stop 1" (SS1)
Required when used in Basic and/or Extended Functions
This test is also required if you are not explicitly using SS1, but just one function for
which STOP B occurs as an error response.
Alternatively, you can also carry out the quantitative test using STOP B yourself, if you
use the tables from sections Acceptance test for Safe Stop 1 with encoder (Ext
ended
Functions) (Page 483) or Acceptance test for Safe Stop 1 without encoder (Ext
ended
Functions) (Page 511).
Tra
ce recordi
ng only required if Extended Functions are used