Safety Integrated Functions
8.5 Safety Integrated Extended Functions
Function Manual
400 Function Manual, 01/2011, 6SL3097-4AB10-0BP3
Note
A delay time between STOP F and STOP B should only be set if an additional response is
initiated during this time when the "Internal Event" (r9722.7) message signal is evaluated.
A monitoring function should also always be active even in automatic mode (e.g. SLS with a
high limit speed) when the delay time is used.
An activated hysteresis for SSM should be regarded as an activated monitoring function.
On delays at the stop response transitions
● t
B
: p9356/p9556
● t
C
: p9352/p9552
● t
D:
p9353/p9553
● t
F1
: p9658/p9858
● t
F2
: p9355/p9555
● n
shutdown
: p9360/p9560
Stop response priorities
Table 8- 12 Stop response priorities
Priority classes Stop response
Highest priority STOP A
..... STOP B
... STOP C
.. STOP D
.. STOP E
Lowest priority STOP F