Safety Integrated Functions
8.7 Commissioning
Function Manual
438 Function Manual, 01/2011, 6SL3097-4AB10-0BP3
● Change/activate settings
– Change settings
You can select this button and enter the password in order to edit the configuration
data. The button function changes to "Activate settings".
– Activate settings
This function accepts your parameter settings, calculates the actual CRC, and
transfers this to the target CRC.
The parameters are only activated after a restart.
Subsequently, a message is output prompting you to save the project and then restart
the system. An acceptance test is also required.
● Change password (p10061 ... p10063)
In order to change the password, enter the old password (factory setting: 0) and then
enter and confirm the new password.
● Restore Safety factory settings
Click this button and then enter the Safety password. The "Restore Safety factory
settings" dialog box opens.
Note
For complete details on the configuration screen, refer to the STARTER online help.