Communication
9.2 Communication according to PROFIdrive
Function Manual
Function Manual, 01/2011, 6SL3097-4AB10-0BP3
551
E_DIGITAL
MT_ZSW
MTn_ZS_F/MTn_ZS_S
CU_ZSW1
These process data are part of the central process data.
MELDW (message word)
See function diagram [2456]
Table 9- 18 Description of MELDW (message word)
Bit Meaning Remarks Parameter
1 Ramp-up/ramp-down completed.
The ramp-up procedure is completed once the
speed setpoint has been changed.
1/0 Ramp-up starts.
The start of the ramp-up procedure is detected as
follows:
The speed setpoint changes,
and
The defined tolerance bandwidth (p2164) is
exited.
0 Ramp-function generator active
The ramp-up procedure is still active once the
speed setpoint has been changed.
0 Ramp-up/ramp-down
completed/ramp-function generator
active
0/1 Ramp-up ends.
The end of the ramp-up procedure is detected as
follows:
The speed setpoint is constant,
and
The actual speed value is within the tolerance
bandwidth and has reached the speed setpoint,
and
The delay time (p2166) has elapsed.
BO: r2199.5
1 Torque utilization < p2194
The current torque utilization is less than the set
torque utilization threshold (p2194),
or
Ramp-up is not yet complete.
1 Torque utilization < p2194
0 Torque utilization > p2194
The current torque utilization is greater than the
set torque utilization threshold (p2194).
BO: r2199.11