Commissioning with PROFIBUS
3.4 Creating a project in STARTER
Function Manual
54 Function Manual, 01/2011, 6SL3097-4AB10-0BP3
What to do? How to do it? Remark
2. Add individual drive Operator action:
→ Double-click "Add individual drive unit".
Device type: SINAMICS S110 CU305 DP (can be
selected)
Device version: 4.1x (can be selected)
Address type: PROFIBUS/USS/PPI (can be selected)
Bus address: 37 (can be selected)
Information about the bus
address:
When commissioning the system
for the first time the PROFIBUS
address of the Control Unit must
be set here.
The address is set via the
address switch on the Control
Unit (or via p0918 if the address
switch = "all ON" or "all OFF"
(factory setting = 126)).
3. Configure the drive unit. Once you have created the project, you have to configure the drive unit. The "Example of
first commissioning using STARTER" chapter contains an example scenario.