Communication
9.2 Communication according to PROFIdrive
Function Manual
570 Function Manual, 01/2011, 6SL3097-4AB10-0BP3
A_DIGITAL (digital outputs)
This process data can be used to control the Control Unit outputs.
See function diagram [2497]
Table 9- 28 Description of A_DIGITAL (digital outputs)
Bit Meaning Remarks Parameter
0 Digital input/output 8
(DI/DO 8)
– DI/DO 8 on the Control Unit must be parameterized as an output
(p0728.8 = 1).
BI: p0738
1 Digital input/output 9
(DI/DO 9)
– DI/DO 9 on the Control Unit must be parameterized as an output
(p0728.9 = 1).
BI: p0739
2 Digital input/output 10
(DI/DO 10)
– DI/DO 10 on the Control Unit must be parameterized as an output
(p0728.10 = 1).
BI: p0740
3 Digital input/output 11
(DI/DO 11)
– DI/DO 11 on the Control Unit must be parameterized as an output
(p0728.11 = 1).
BI: p0741
4...15 Reserved – – –
Note:
The bidirectional digital inputs/outputs (DI/DO) can be connected as either an input or an output (see also transmit signal
E_DIGITAL).
MT_STW
Control word for the "central probe" function. Display via r0685.
Table 9- 29 Description of MT_STW (control word for Control Unit)
Bit Meaning Remarks Parameter
0 Falling edge probe 1 –
1 Falling edge probe 2 –
2 Falling edge probe 3 –
3 Falling edge probe 4 –
4 Falling edge probe 5 –
5 Falling edge probe 6 –
Activation of measuring time determination with the next falling edge
6...7 Reserved – –
8 Rising edge probe 1 –
9 Rising edge probe 2 –
10 Rising edge probe 3 –
11 Rising edge probe 4 –
12 Rising edge probe 5 –
13 Rising edge probe 6 –
Activation of measuring time determination with the next rising edge
14...15 Reserved – –
CI: p0682