Commissioning with CANopen
4.2 Commissioning
Function Manual
82 Function Manual, 01/2011, 6SL3097-4AB10-0BP3
Parameter p8609
Sets the behavior of the CAN node referred to the communications error or equipment fault.
Values:
0: Pre-operational
1: No change
2: Stopped
Index (corresponds to the CANopen object 1029 hex):
[0] = Behavior for communication errors
[1] = Behavior for device faults