B.1.3 Updating the Electronic Device Description (EDD)
Procedure
1. Check that the EDD revision match the Firmware revision in the device according to the table
in section Product compatibility TH320/420 (Page 10).
2. Go to the support page Software downloads (
http://www.siemens.de/
prozessinstrumentierung/downloads).
3. Enter the product name in the eld "Enter search term...".
4. Download the most current EDD of your device.
5. Save les to your computer in an easily accessed location.
6. Launch SIMATIC PDM – Device Integration Manager.
From the File menu, click "Read device descriptions from compressed source...".
7. Browse to the zipped EDD le, select and open it.
8. Use the "Integration" function to integrate the EDD into the device catalog. The EDD is now
accessible via SIMATIC Manager.