Enter the calibration points within the measuring range using the remote operation.
8.4.5.2 Setting one-point calibration
Requirement
The measured value for the low calibration point is stable.
There is no sensor error.
The measured value is in the measuring range.
Procedure
1. Select the menu command "Maintenance > Calibration".
2. Select the tab input 1 or input 2.
3. Bring the sensor to a stable temperature environment. For example, 0 °C.
The 󹪞uctuation of the measured value is within the precision requirements.
We recommend use of a calibrator, e.g. from Beamex.
4. Click the "One-point calibration" button.
5. Con󹪝rm the warnings.
6. When your measured value is stable, assign the measured value to the low calibration point
of the device.
Result
The device calibrates to the measured value.
The device moves the characteristic by the di󹪜erence between the original and the new
calibration point.
Parameter assignment
8.4 Assigning parameters using remote operation
SITRANS TS100/TS200/TS300/TS500/TSinsert/TSthermowell
Operating Instructions, 08/2020, A5E47810090-AA 99

Table of Contents

Other manuals for Siemens SITRANS TSinsert

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SITRANS TSinsert and is the answer not in the manual?

Siemens SITRANS TSinsert Specifications

General IconGeneral
BrandSiemens
ModelSITRANS TSinsert
CategoryTemperature Controller
LanguageEnglish

Related product manuals