Sensor calibration (Page 98)
Transmitter sensor matching (Page 101)
Operating hours counter (Page 102)
Current output (Page 103)
8.3 Parameter assignment over device with display
Introduction
This section describes all parameters that you can reach over the device with a display.
You will nd information on operating the device with display in the section Operating the
device with display (Page 60).
You can nd the list of available parameters with ID and parameter name in the section List of
parameters on the display (Page 62).
8.3.1 Input type 1 [01]
Selects the input type 1.
Indication on the display Meaning
Setting range:
P100I Pt100 - IEC 751
P500I Pt500 - IEC 751
P1k I Pt 1000 - IEC 751
TC B TC Type B - IEC 584
TC E TC Type E - IEC 584
TC J TC Type J - IEC 584
TC K TC Type K - IEC 584
TC N TC Type N - IEC 584
TC R TC Type R - IEC 584
TC S TC Type S - IEC 584
TC T TC Type T - IEC 584
TC L TC Type L - IEC 584
TC U TC Type U - DIN 43710
Factory setting: P100I Pt100 - IEC 751
Parameter assignment
8.3 Parameter assignment over device with display
SITRANS TS100/TS200/TS300/TS500/TSinsert/TSthermowell
74 Operating Instructions, 08/2020, A5E47810090-AA