A technical standard is in e󹪜ect for mounted or installed components (terminal
compartments, sockets, cable entry 󹪝xtures, plug-in connectors) that meets at least the
speci󹪝cations in the certi󹪝cate of conformity; a separate test certi󹪝cate must also have been
issued for these components.
Use the device to measure temperatures in accordance with the technical speci󹪝cations for
the maximum ambient temperatures in the connection area of the sensor. See sections Gas
hazardous area: Ex d / XP (Page 135) and Dust hazardous area: Ex i / IS / Ex tb / DIP (Page 137).
2.4.2 For SITRANS TSinsert/TS100/TS200/TS500
NOTICE
Ambient temperature too high
Damage to cable sheath.
At an ambient temperature ≥ 60 °C (140 °F), use heat-resistant cables suitable for an
ambient temperature at least 20 °C (36 °F) higher.
Safety notes
2.4 Use in 󹪞ameproof enclosures "d" and protection in enclosures "tb"
SITRANS TS100/TS200/TS300/TS500/TSinsert/TSthermowell
Operating Instructions, 08/2020, A5E47810090-AA 17

Table of Contents

Other manuals for Siemens SITRANS TSinsert

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SITRANS TSinsert and is the answer not in the manual?

Siemens SITRANS TSinsert Specifications

General IconGeneral
BrandSiemens
ModelSITRANS TSinsert
CategoryTemperature Controller
LanguageEnglish

Related product manuals