Effekta
3. If no further inverter connected, terminate the inverter:
Set the jumper on the RS485 interface card to ON.
4. Close the inverter if no other inverters are to be connected.
5. Insert the terminal block connector into the Solar-Log™ RS485 socket.
Connect the inverters to each other
Connect using a 3 wire, shielded data cable
Where to connect: Terminal strip inside the inverter (on the retrofitted RS485 interface).
Procedure
1. Open the inverter as shown in the inverter's instructions.
2. Using the data cable connect terminals "Pin 2-RS485-A (+)", "Pin 3-GND" and "Pin 1-RS485-B (-)" of inverter 1 to
the corresponding terminals on inverter 2.
3. Connect the other inverters to each other in the same way.
4. Terminate the last inverter.
Set the jumper on the RS485 interface card to ON.
5. Close inverters.
Allocate communication address
Recommendation: Continuous numbering starting with 1.
Setting: Using the inverter operating display
Procedure: Start according to the inverter's instructions