SolarEdge
87SolarEdge
87.1 SolarEdge
Termination Addressing Interface
Switch Yes RS485
Overview
Integrated interface
Where to connect: Terminal strip inside the inverter
Communication address must be allocated
3-pin wiring
Installation steps
Switch off the inverters and Solar-Log™
Connect inverters to the Solar-Log™
Address inverter and set protocol
Connect the inverters to each other
Note
Installing a “SolarEdge-Gateway” on a RS485 bus, connecting SolarEdge inverters with a Solar-Log™,
can lead to communication problems with the inverters. In order to ensure a correct communication
with the Solar-Log™, the “Wireless package” switch must be activated on the respective I/O port in the
web menu.
The SolarEdge-Gateway is not supported on I/O port “C”, which has no wireless package option.