General Electric inverters (GE)
34 GeneralElectricinverters(GE)
34.1 GeneralElectricinverters(GE)
Termination Addressing Interface
No Yes LAN
Overview
Integrated interface.
Connected using network cable (patch cable) and Ethernet router or switch.
Communication address must be allocated.
Installation steps:
Allocate communication address.
Connect inverters to the Solar-Log™.
Connect the inverters to each other.
Allocate communication address
Recommendation: Continuous numbering starting with 1.
Setting: Using the inverter operating display.
Procedure: Before connecting to the Ethernet router or switch and allocating the IP address.
Connect inverters and the Solar-Log™.
The wiring is done using a
network cable (patch cable/crossover cable) and the
Ethernet router or switch.
Procedure
1. Set different unit IDs on each inverter in accordance with the inverter's instructions.
2. Connect the Solar-Log™ and the inverter to the router or switch.
3. Allocate an IP address to each inverter using the manufacturer's IP setting kit:
The first three number blocks like the Solar-Log™, e.g.
192.168.178.49.
The fourth number block: an address that is available, e.g. 192.168.178.50.
Details on using the IP setting kit can be found in the manufacturer's SVT monitoring manual.
Note
A maximum of 32 inverters can be connected to the interface.