116
Eltek
28 Eltek
28.1 Eltek
Termination Addressing Interface
Yes Yes RS485
Select „Eltek: Theia HE-t/HE-t UL“ during the inverter detection
Overview
•
Integrated interface.
•
Where to connect: Terminal strip inside the inverter.
•
2-pin wiring.
•
Communication address must be allocated.
•
Installation steps:
• Switch off the inverters and Solar-Log™.
• Connect inverters to the Solar-Log™.
• Connect the inverters to each other.
• Configure the inverter's communication interface.
• Allocate communication address.
Connect inverters to the Solar-Log™
The wiring is done using a
•
self-made, shielded 2 wire data cable and terminal block connector.
Procedure
1. Connect wires as shown in the diagram below:
Solar-Log™ terminal strip connector Inverter terminal strip
Terminal Terminal
► 1 ► B (Data+)
► 4 ► A (Data-)
2. If no further inverter is connected, terminate the inverter according to the instructions for the inverter.
3. Close the inverter cover if no other inverters are to be connected.
4. Insert the terminal block connector into the Solar-Log™ RS485 socket.
Connect the inverters to each other
The inverters are connected together using the RS485 interface. Refer to the manufacturer's inverter manual for
the details on how to setup the connection.
Allocate communication address
•
Recommendation: Continuous numbering starting with 1.
•
Setting: Using the inverter operating display.
•
Procedure: Start according to the inverter's instructions.