387
Würth
108 Würth
108.1 WürthSolarStar-Series
Termination Addressing Interface
No Yes RS485
Select “SolarMax” during the inverter detection
Supported Models:
•
SolarStar a2000
•
SolarStar a3000
•
SolarStar a4200
•
SolarStar a6000
Overview
•
Integrated interface
•
Where to connect: RJ45 socket on the outside of the inverter
•
6-pin wiring
•
Communication address must be allocated.
•
Installation steps
• Switch off the inverters and Solar-Log™
• Connect inverters to the Solar-Log™
• Connect the inverters to each other
• Allocate communication address
Connect inverters to the Solar-Log™
The wiring is done using a
•
ready-made data cable (optional extra; not supplied)
or
•
self-made RS485 data cable with RJ45 plug and terminal block connector.
Caution
Risk of damage to the unit!
The Solar-Log™ also has an RJ45 socket, which must never be connected to the RJ45 socket on the
inverter.
► Only connect inverters via the RS485/422 Solar-Log™ interface(s).