Termination Addressing Interface
No Yes RS485
Overview
Interface not integrated; Retrofit RS485 interface card
6-pin wiring
Communication address must be allocated
Installation steps
Switch off the inverters and Solar-Log™
Install the RS485 interface in the inverter
Connect inverters to the Solar-Log™
Connect the inverters to each other
Allocate communication address
Installing the RS485 interface
Procedure
Install the RS485 interface in the inverter in accordance with the interface card installation instructions.
Connect inverters to the Solar-Log™
The wiring is done using a
ready-made data cable (optional extra; not supplied)
or
self-made cable connection using RS485 data cable with RJ45 plug and terminal block connector
Caution
Risk of damage to the unit!
The Solar-Log™ also has an RJ45 socket, which must never be connected to the RJ45 socket on the
inverter.
Only connect inverters via the RS485/422 Solar-Log™ interface(s).
Procedure
1. Open the inverter as shown in the inverter‘s instructions.
2. If you are making the cable yourself, connect the wires as shown in the following diagram:
Solar-Log™ terminal strip connector RJ45 inverter
Terminal PIN
1 7
2 1
2 2
3 3
3 4
5 - unused
6 - unused
4 8