Conergy
18 Conergy
18.1 Conergy(onlySolar-Log1000,1900and2000)
Note
Conergy inverters can only be connected to the Solar-Log 1000, 1900 and 2000, as only this one has a
CAN interface.
The following description relates to inverters without transformers produced in or after 2007.
Termination Addressing Interface
Yes No CAN bus
Overview
CAN only to be used on Solar-Log 1000, 1900 and 2000 (CAN interface).
Integrated interface.
Where to connect: CAN socket on the outside of the bottom of the inverter.
Only use ready-made cable sets.
Two different special cable sets must be ordered separately.
- Prefabricated cable set between the Solar-Log 1000, 1900 and 2000 and the first inverter, including cable
termination.
- Ready-made cable set with 5 pin Phoenix contact connection plug for connecting the inverters to each
other.
- Depending on the number of inverters several of these cables will be required.
Maximum total cable length: 200 m
Communication address does not have to be assigned.
Installation steps:
Switch off the inverters and Solar-Log™.
Connect inverters to the Solar-Log™.
Connect the inverters to each other.
PIN assignment:
Solar-Log™ terminal strip connector Sensor / actuator connector 5-pin
Terminal Pin
4 not used 1 not used
5 not used 2 not used
1 3
3 4
2 5
At Solarlog ™ set a 120 resistor between PIN 2 and 3.