Termination Addressing Interface
Yes Yes RS485
Overview
Integrated interface
Where to connect: Terminal strip behind service cover
2-pin wiring
Communication address must be allocated
Installation steps
Switch off the inverters and Solar-Log™
Connect inverters to the Solar-Log™
Connect the inverters to each other
Allocate communication address
Connect inverters to the Solar-Log™
The wiring is done using a
self-made, shielded 2 wire data cable with a terminal block connector.
Procedure
1. Open the inverter as shown in the inverter's instructions.
2. If you are making the cable yourself, connect the wires as shown in the following diagram:
Solar-Log™ terminal strip connector Terminal strip inside the inverter
Terminal Terminal
1 A-Data +
4 B-Data -
3. Terminate the inverter as shown in the inverter's instructions.
4. Close inverters.
5. Insert the terminal block connector into the Solar-Log™ RS485 socket.
Connect the inverters to each other
Where to connect: Terminal strip behind service cover
2-pin wiring