JFY
Connect the inverters to each other
•
Connect using a network cable (patch cable)
•
Where to connect: RJ45 sockets on the outside of the inverter.
Procedure
1. Insert the RJ45 plug into any RJ45 socket on inverter 1.
2. Insert the other end of the wire into any RJ45 socket on inverter 2.
3. Connect the other inverters to each other in the same way.
4. Terminate the last inverter.
Insert the 120 Ω resistor into the free RJ45 socket.
Allocate communication address
•
Recommendation: Continuous numbering starting with 1. (1-250)
•
Setting: Using the inverter operating display
•
Procedure: Start according to the inverter‘s instructions
Note
A maximum of 31 inverters can be connected per RS485 bus.
New supported models ( as of firmware 4.2.2):
•
SUNTREE 25000TL+, SUNTREE 28000TL+, SUNTREE 50000TL+