237
Q3
Connect the inverters to each other
Connection in the master-slave data network using an 1:1 cable with M12 plug connector (available as an
optional extra from Q3). Sockets X6 and X7 are connected to each other electrically.
Where to connect: Round pin plug on the outside of the inverter.
Procedure
1. Insert the plug into the X6 socket on inverter 1.
2. Insert the other end of the wire into the X7 socket on inverter 2.
3. Connect the other inverters to each other in the same way.
4. Terminate the last inverter according to the manufacturer‘s instructions.
Allocate communication address
Setting: Using the inverter‘s control panel.
Recommendation: Continuous numbering starting with 1.
Procedure: Start according to the inverter‘s instructions