Procedure:
1. Open the inverter according to the inverter‘s instructions.
2. Connect the wires for the cable connection as shown in the following diagram:
Solar-Log™ terminal strip connector Terminal strip inverter RS485 A
Terminal PIN assignments for RS485 A
► 1 Data+ ► A1
► 4 Data- ► B1
3. Terminate the inverter according to the inverter‘s instructions if no additional inverters are to be connected.
4. Close the inverter if no other inverters are to be connected.
5. Insert the terminal block connector into the Solar-Log™ RS485 socket.
Connect the inverters to each other
•
Where to connect: Terminal strip inside the inverter.
•
Connect the inverters to each other according to the inverter instructions
Assign the communication address
•
Recommendation: Continuous numbering starting with 1 going to 50.
•
Setting: Using the inverter‘s operating display.
•
Procedure: Start according to the inverter‘s instructions.