286
Siemens
How to set communication address parameters
1. Select "USS address" and press ENTER.
2. Enter the numerical value xx [Address] and press ENTER.
3. Select "Baud rate" and press ENTER.
4. Enter the numerical value [Baud rate] and press ENTER.
5. Select "Protocol" and press ENTER.
6. Select protocol type "1" and press ENTER.
After the parameters have been set on the display the inverter must be switched off for one minute using the
installed DC isolation switch. The settings are now applied and set to active. The configuration procedure is descri-
bed in the manufacturer's handbook. Starting with Solar-Log
TM
firmware version 2.0.3 (Nov.09) no other parame-
ters must be set on the inverter. The setting up (commissioning) can be continued immediately.
Solar-Log™ compatibility with older PVM installations
With older Solar-Log™ / PVM installations the inverter had to be set with additional parameters for Solar-Log™
compatibility. This is only still necessary if an inverter has been replaced because it was faulty or if the system has
been extended. Only in these cases must the additional parameters be set again on the new inverters.
Note
A maximum of 31 inverters can be connected per RS485 bus.