Steca
Connect the inverters to each other
Connect using
a 2-wire shielded data cable and
4-pin Phoenix Contact Connection plug type "M12MS SACC-4SC SH“ (two plugs included with the inverter).
Where to connect: RS485 sockets on the bottom of the inverter.
The RS485 IN and OUT sockets are each double connections so that the wiring can be continued to the next inver-
ter.
Procedure
1. Wiring the data cable to the "Phoenix Contact Type M12MS SACC-4SC SH“ according to the manufacturer's
instructions.
2. Insert one plug into the OUT (X14B) socket of inverter 1.
3. Insert the other end of the wire into the IN socket (X15B) on inverter 2.
4. Connect the other inverters to each other in the same way.
5. Terminate the last inverter.
On the sockets "RS485 OUT" with Phoenix contact type M12MS SACC-4SC SH bridge the connections PIN1 to
PIN2 and PIN3 to PIN4.
6. Close inverters.
Allocate communication address
Recommendation: Continuous numbering starting with 1.
highest possible address: 31
Set the following parameters on the inverter's operating display:
Press "F1", select Numerical list, press "ENTER".
Set parameter number 2000 [password protection],
press "ENTER" twice.
Enter 72555, press "ENTER"
Set parameter number 0406, press "ENTER"
Select sub parameter 0406,3, press "ENTER"
Enter figure for communication x
[
x = continuous numbering starting with 1; highest possible address: 31], press "ENTER". 31], press "ENTER".
After configuring on the display:
Using the installed DC isolating switch turn the inverters on and off briefly so that the settings are activated.
Set the date and time on the inverter as shown in the inverter instructions.