Note
The Inepro 75D cannot be used on the same bus input with RS422 connected inverters.
Note
The Inepro 75D meters are automatically assigned the mod bus address 234 by Solar-Log™ during the
detection process.
This address is therefore not allowed to be used for other devices.
After the configuration, the display on the Inepro meter alternates between the meter status and the
address display (ID=EA). This can be used to check if Solar-Log™ has correctly detected the meter.
All RS485 meters have to be terminated with a 120Ω resistor between the two pins used.