Testing record for Aspirating Smoke Detection System of the TITANUS MICRO · SEN
type
Device number
Detection unit serial number
Device base serial number
Commissioning
Visual check
(9/ –)
Low pressure [Pa]
Sensitivity [%/m]
Alarm delay [s]
Air flow range [10-50%]
Fault delay [min]
Fault storing (ja/nein)
Dynamic air flow (ja/nein)
Location (ja/nein)
LOGIC · SENS
(ja/nein)
Air pressure-dependent adjustment (ja/nein)
Air pressure-independent adjustment (ja/nein)
Height [m ü. NN.]
Air pressure [hPa]
Ventilator voltage [9-13,5V]
Air flow range [m/s]
Temperature [°C]
Blockage Fault
LED flashing
(9/ –)
Relay drops out after delay time
(9/ –)
Signal forwarding to fire alarm system
(9/ –)
Cause removed, LED out
(9/ –)
Relay picks up after threshold undercut
(9/ –)
Cause removed, LED stored
(9/ –)
Relay remains down for at least 100 secs
(9/ –)
Break Fault
LED flashing
(9/ –)
Relay drops out after delay time
(9/ –)
Signal forwarding to the FAS
(9/ –)
Cause removed, LED out
(9/ –)
Relay picks up after threshold undercut
(9/ –)
Cause removed, LED stored
(9/ –)
Relay remains down for at least 100 secs
(9/ –)
Main Alarm
LED flashing
(9/ –)
Relay picks up after delay time
(9/ –)
Signal forwarding to FAS
(9/ –)
LED stored
(9/ –)
Relay stored
(9/ –)
Location (ROOM-IDENT)
Free blow time [10-255s]
Free blow ventilator [9-13,5V]
Aspiration ventilator [9-13,5V]
LED Location long-term aspiration aperture A (yes/no) / [s]
LED Location long-term aspiration aperture B (yes/no) / [s]
LED Location long-term aspiration aperture C (yes/no) / [s]
LED Location long-term aspiration aperture D (yes/no) / [s]
LED Location long-term aspiration aperture E (yes/no) / [s]
Reaction Indicator
Aspiration aperture A (yes/no)
Aspiration aperture B (yes/no)
Aspiration aperture C (yes/no)
Aspiration aperture D (yes/no)
Aspiration aperture E (yes/no)
Issuer: …………………………… Signature: …………………………………
Key: 9 O.K.
– not O.K.
Measure/ +
Setting
Measure/ +
Setting
Measure/ +
Setting
Measure / +
Setting
Measure/ +
setting
Measure/ +
Setting