EasyManua.ls Logo

Xinje XD Series - 5-6 AB phase counting frequency doubling setting

Xinje XD Series
456 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
209
X030
U
X031
X032
X033
U
X034
XD5-60T10, XDM-60T10, XD5E-60T10, XDME-60T10, XL5E-64T10, XLME-64T10
AB phase mode
HSC0
HSC2
HSC4
HSC6
HSC8
HSC10
HSC12
HSC14
HSC16
HSC18
HSC20
HSC22
Max frequency
50K
50K
50K
50K
50K
50K
50K
50K
50K
50K
Quadruple
frequency
2/4
2/4
2/4
2/4
2/4
2/4
2/4
2/4
2/4
2/4
Counter
interruption
X000
A
X001
B
X002
Z
X003
A
X004
B
X005
Z
X006
A
X007
B
X010
Z
X011
A
X012
B
X013
Z
X014
A
X015
B
X016
Z
X017
A
X020
B
X021
Z
X022
A
X023
B
X024
Z
X025
A
X026
B
X027
Z
X030
A
X031
B
X032
Z
X033
A
X034
B
X035
Z
5-6 AB phase counting frequency doubling setting
For AB phase counting, the double frequency number can be set in special FLASH data
registers SFD321, SFD322, SFD323... SFD330, 2 means double frequency; 4 means
quadruple frequency.
Register
name
Function
Setting value
Meaning
SFD320
HSC0 frequency
doubling
2
2 frequency doubling
4
4 frequency doubling
SFD321
HSC2 frequency
2
2 frequency doubling
tudonghoatoancau.com

Table of Contents

Other manuals for Xinje XD Series