8Alarm
DX100 8.3 Alarm Message List
8-547
5 Incorrect designation of the control
method for sealer gun control
Setting error (1)Check the following settings.
·If "1" is set for PRM1 of the OPTON instruction, set the PRM2 needle
position designation to a value between 0 and 100.
6 Incorrect designation of the sealing
width for sealer gun control
Setting error (1)Check the following settings.
·If "2" is set for PRM1 of the OPTON instruction, set PRM2 sealing width
designation to a value between 0 and 30.
4614 UNDEFINED
SEALERGUN
COND FILE
Setting error (1)Check the following settings.
·Check the settings for servo sealer gun condition file.
4615 I/O AXIS
OPERATING
An attempt was made to command
a job whose control group was in I/
O axis motion.
Setting error (1)Check the following settings.
·Does not the I/O axis motion executed for the control group that executing
the job·
·Does not the job executed for the control group that operating by the I/O axis
motion·
The control group where the I/O axis is operating cannot execute the job.
Moreover, the I/O axis motion cannot perform for the control group where the
job is executing.
4616 AXIS SHIFT
ERROR
1 The file could not be switched
because of incorrect start point
designation.
Software operation
error occurred
(1)Reset the alarm, and then try again.
(2)If the alarm occurs again, save the CMOS.BIN in maintenance mode, and
then contact your Yaskawa representative about occurrence status
(operating procedure).
2 The control group with which the
axis shifting is performed
disagrees with the control group
set for the axis shifting function in
the calibration file.
Software operation
error occurred
(1)Reset the alarm, and then try again.
(2)If the alarm occurs again, save the CMOS.BIN in maintenance mode, and
then contact your Yaskawa representative about occurrence status
(operating procedure).
3 The calibration file number for axis
shifting function is out of the
applicable range.
Setting error (1)Check the following settings.
·Correct the settings for the OPTON instruction tag so that value of the file
number specification is 1 to 32.
Alarm
Number
Alarm Name Sub
Code
Meaning Cause Remedy