8Alarm
DX100 8.3 Alarm Message List
8-549
2 An attempt was made to obtain the
step that used a local position type
variable. (The step with local
position type variable cannot be
fetched. Example: MOVJ LP000
VJ=25.00)
Setting error (1)Check the following settings.
·Check the settings for the GETPOS instruction.
3 The specified step did not exist. Setting error (1)Check the following settings.
·Check the settings for the GETPOS instruction.
4624 PLUG VOLUME
SETTING ERROR
Setting error (1)Check the following settings.
·Check the setting for the amount of fillings.
4625 WRONG
EXECUTION OF
LOADDB INST
1 No file Software operation
error occurred
(1)Reset the alarm, and then try again.
(2)If the alarm occurs again, save the CMOS.BIN in maintenance mode, and
then contact your Yaskawa representative about occurrence status
(operating procedure).
2 No directory Software operation
error occurred
(1)Reset the alarm, and then try again.
(2)If the alarm occurs again, save the CMOS.BIN in maintenance mode, and
then contact your Yaskawa representative about occurrence status
(operating procedure).
4 There was no directory entry after
this point.
Software operation
error occurred
(1)Reset the alarm, and then try again.
(2)If the alarm occurs again, save the CMOS.BIN in maintenance mode, and
then contact your Yaskawa representative about occurrence status
(operating procedure).
-1 No file name Software operation
error occurred
(1)Reset the alarm, and then try again.
(2)If the alarm occurs again, save the CMOS.BIN in maintenance mode, and
then contact your Yaskawa representative about occurrence status
(operating procedure).
Alarm
Number
Alarm Name Sub
Code
Meaning Cause Remedy